NA2XBY

التطبيق
These power and fixed wiring cables are used in low voltage
installation systems. They are well adapted to underground
use in industrial applications with an additional mechanical
protection. These cables can be fixed on cable trays, within
conduits or fixed to walls & where the cable may be subject
to mechanical crush and impact.
الإنشاءات
| قائد الفرقة الموسيقية | Round Stranded Aluminum as per class 2 of IEC 60228 |
|---|---|
| العزل | XLPE applied around the conductor for 90 c |
| الألوان | Color: can be supplied on request. |
| Assembly | Cores laid up, filled with non-hygroscopic material, covered with mylar tape and extruded |
| Armor | Galvanized Steel Tape Armor applied as per IEC 60502-1 |
| الغمد | PVC Applied for 90 c |
| التعبئة | Cables to be supplied in wooden drum |
التقييمات
| درجة الحرارة | - 25 C to + 90 C |
|---|---|
| الفولتية | 600/1000 V |
| المعايير المطبقة | IEC 60228, IEC 60502-1 |
| Flame Retardant | IEC 60332-1 |

Conductor Flexibility Class 2 IEC 60228

Rated Voltage 600/1000 V

Minimum Bending Radius (mm) 10 x Overall Diameter

Max conductor Temp in service 90 C

Max. short-circuit temperature: 250°C Minimum installation and handling temperature: 5ºC

Flame retardant IEC 60332-1